Star 2000 Range
UPS Specifications |
Power Factor Correction |
Voltage 230V – 35% +20% (150V~276V) 8V
Hysteresis |
Frequency: +/-10% Phase Locked |
Phase Lock: 4Hz/Sec |
|
Output |
Voltage 220/230V/240 selectable ± 1.5% |
Voltage 110Vac via Output Isolating Transformer |
Derating with input V Vmains<184V 0.6% Pnom
/Volt (-20%V) |
Voltage distortion <2% with linear load |
Frequency with mains (PLL) +/-10% free running 50
or 60 Hz +/-0.15Hz |
Overload 125% for 4 sec (with mains present) |
Crest Factor 3:1 (Ipk/Irms with standard
non-linear load) |
AC/AC efficiency 90% (On Line) / 97% (ECO MODE) |
|
By-Pass |
Voltage range +/- 20% and hysteresis of 8V |
Frequency range +/-10 %
|
|
Batteries |
Recharge time 12 hours for 90% of Cn |
|
Marine UPS Cabinets |
LxDxH [mm] 230x640x620 |
Weight:- 3Kva (80Kg), 5Kva (92Kg), 6Kva (95Kg) |
|
Communications |
Interfaces Optoisolated contacts for mains
failure & battery low |
RS232 / RS485 data ports |
|
Environment |
Temperature / Humidity 0 min.~45 °C max. / 0~90%
non-condensing |
25 °C for longer battery life |
Noise level < 65 dB at 1Mt. Ambient
temperature 25°C |
|
Standards |
This series is designed to comply with the
following Environmental and generator specifications:
-
Lloyds
- DNV
- DEF 61-5 Part 4
- EN60529
- EN 50091-1 (safety)
- EN 50091-2 level A (EMC)
|